Description
Description
Standards
-
ProductIEC 60502; NF C32-207/A1
Application
A05VV-U/R cables are designed for households. They can only be used for heating and cooking appliances if there is no risk of radiations or contact with hot parts.
Installation and design
Installation
Open air.
Sheath colour
Black. Others under request
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Sheath colour
Black
Conductor flexibility
Solid class 1
Conductor material
Bare copper
Insulation
PVC
Outer sheath
PVC
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
1.5 mm²
Number of cores
2
Approximate weight
130 kg/km
Maximum outer diameter
10.5 mm
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
300/500 V
Permissible current rating in open air
20 A
Voltage drop, single phase
23.0 V/A.km
Mechanical characteristics
Mechanical characteristics
Mechanical resistance to impacts
Low
Cable flexibility
Rigid
Usage characteristics
Usage characteristics
Length
1000 m
Packaging
Drum
Flame retardant
C2, NF C 32-070
Weather resistance
Good
Max. conductor temperature in service
70 °C
Chemical resistance
Accidental
Operating temperature, range
-5 ... 60 °C
Short-circuit max. conductor temperature
150 °C
Water proof
Accidental
Bending factor when laying
3 (xD)
Resources
Resources
Documentation
Homologation certificate (pdf)
pdf — 213.1 kB
H05VV-F datasheet
pdf — 89.6 kB
Our websites